The cleanroom class you write into a brief is one of the most expensive lines in the project. Each step tighter means more air, more filters, more energy and stricter discipline, every day for the life of the facility.
Specify too loose and the product, the audit or the yield fails. Specify too tight and you pay for cleanliness the process never needed.
This guide, from the engineers at Prana Build Tech, explains how ISO 14644 classes work, how they map to the GMP grades used in pharma, which classes different industries actually need, and what each step tighter means for the building.
The classes at a glance
ISO 14644-1 defines nine classes, from ISO 1 (cleanest) to ISO 9, by the maximum number of airborne particles allowed per cubic metre of air. Each class allows ten times more particles than the one before it. Most pharma and electronics facilities work between ISO 5 and ISO 8.
| ISO class | Max particles ≥ 0.5 µm per m³ | Old US name (FS 209E) | Typical use |
|---|---|---|---|
| ISO 4 | 352 | Class 10 | Semiconductor wafer processing |
| ISO 5 | 3,520 | Class 100 | Aseptic filling zones, critical semiconductor and optics work |
| ISO 6 | 35,200 | Class 1,000 | Electronics assembly, some device manufacturing |
| ISO 7 | 352,000 | Class 10,000 | Background rooms for aseptic work, medical devices, compounding |
| ISO 8 | 3,520,000 | Class 100,000 | Oral solid dosage, packaging, gowning and support areas |
| ISO 9 | 35,200,000 | — | Close to normal room air; rarely specified |
How classification works
A cleanroom is classified by counting airborne particles at set locations with a light-scattering particle counter and comparing the counts with the class limits.
What it measures. ISO 14644-1 only classifies particles between 0.1 µm and 5 µm. Larger particles can be described separately with an “M descriptor”, and the standard says nothing about whether particles are living. Microbial limits come from GMP rules, not ISO.
When it is measured. The same room can be classified in three states, and the brief must say which one applies:
- As-built: the finished room with all services running, but no production equipment or people.
- At rest: equipment installed and running, but no personnel present.
- Operational: equipment running and people working normally.
People are the largest source of particles in most cleanrooms, so a room that passes at rest can fail in operation. Design for the state your process and regulator care about.
How often it is re-tested. ISO 14644-2 defaults to annual reclassification, with a risk-based extension. For sterile pharma, EU GMP Annex 1 is stricter: Grade A and B areas every six months at most, and Grade C and D every 12 months. Pressure differentials should be monitored continuously.
ISO classes against GMP Grades A to D
Pharma uses a second vocabulary. EU GMP Annex 1, the WHO GMP guidelines and India’s revised Schedule M grade sterile manufacturing areas from A to D. The grades borrow ISO particle limits but add two things ISO leaves out: a limit for both “at rest” and “in operation”, and limits for microbes.
| GMP grade | ≥ 0.5 µm/m³ at rest | ≥ 0.5 µm/m³ in operation | ISO equivalent (rest / operation) | Typical area |
|---|---|---|---|---|
| A | 3,520 | 3,520 | ISO 5 / ISO 5 | Filling zone, open product, isolators |
| B | 3,520 | 352,000 | ISO 5 / ISO 7 | Background room for Grade A aseptic work |
| C | 352,000 | 3,520,000 | ISO 7 / ISO 8 | Less critical sterile steps, e.g. solution preparation |
| D | 3,520,000 | Set by risk assessment | ISO 8 / — | Component handling, gowning, support areas |
What this means in India. The revised Schedule M was notified in January 2024 to bring Indian GMP in line with WHO standards, and took effect for large manufacturers on 28 June 2024, with extra time given to smaller firms. Alignment is still moving: in October 2026 the Health Ministry proposed amendments to align Grade A microbial limits with WHO. Plants designed today should be designed to the WHO and Annex 1 grade definitions, not just to an ISO class.
Which class does your industry need?
Few facilities are one class throughout. Most are zoned: a small, very clean core inside progressively less clean rooms. These are typical starting points; the product, process and regulator set the final answer.
| Industry and process | Typical class | Notes |
|---|---|---|
| Sterile injectables: aseptic filling | Grade A (ISO 5) in a Grade B background | The strictest pharma zone; typically ISO 5 for aseptic areas, ISO 7 around them and ISO 8 for support |
| Sterile products: preparation and terminally sterilised steps | Grade C or D (ISO 7 or 8) | Set by the risk to the product |
| Semiconductor front-end fab | ISO 1 to ISO 5 | Lithography, etch and deposition need ISO 1, 3 or 5 |
| Semiconductor assembly and test (OSAT) | Often ISO 7, with cleaner zones | One recent OSAT build engineered 14,000 m² of ISO 7 cleanroom; advanced packaging may need tighter zones |
| Medical devices, Class II | ISO 7 or ISO 8 | Commonly ISO 7 or 8; Class III often ISO 5–6 at the point of assembly |
The OSAT row matters locally. With chip-packaging plants now being built in Andhra Pradesh and Telangana, more builders will be asked for ISO 7 halls with ISO 5 or 6 zones, ultra-pure water and tight vibration control. A dedicated guide to building for semiconductor OSAT is in preparation.
What changes as the class tightens
Each step tighter multiplies the air the building must move and filter. That drives the size of the air-handling plant, the plenum above the ceiling, the power supply and the running cost.
| ISO class | Air changes per hour (guide) | HEPA ceiling coverage (guide) | Airflow pattern |
|---|---|---|---|
| ISO 8 | 6–60 | 5–15% | Dilution (non-unidirectional) |
| ISO 7 | 60–150 | 15–20% | Dilution (non-unidirectional) |
| ISO 6 | 150–240 | 25–40% | Dilution or mixed |
| ISO 5 | 240–600 | 35–70% | Usually unidirectional (“laminar”) |
The air is only part of it. A tighter class also changes:
- Pressure cascade: each cleaner room is held at a higher pressure than the room before it, so air always flows from clean to less clean. That needs airlocks, tight doors and continuous monitoring.
- Finishes: smooth, non-shedding walls, coved corners, flush lights and sealed penetrations, so there is nowhere for dust to collect.
- Layout: separate routes for people, materials and waste, with gowning rooms sized for the class.
- Operations: stricter gowning, cleaning and monitoring, which cost money every day after handover.
For how we design and validate cleanroom HVAC, read cleanroom HVAC design and validation.
Five mistakes we see when classes are specified
- One class for the whole floor. Making every room ISO 7 because one process needs it wastes air and energy. Zone the cleanest area tightly and step down around it.
- Not saying “at rest” or “in operation”. A brief that just says “ISO 7” leaves the most important question open. For GMP work, both states matter.
- Designing for the particle count, not the people. Staff numbers, gowning and movement drive contamination. A room sized for four operators will struggle with ten.
- Treating ISO class as GMP compliance. ISO counts particles; GMP also needs microbial limits, monitoring and documented qualification. Plan for both from day one.
- Leaving no room to grow. Air handlers, ducts and ceiling voids sized exactly for today’s class make an upgrade from ISO 8 to ISO 7 a rebuild. A modest margin in the plant is cheap insurance.
If you are planning a pharma facility in Hyderabad, read pharma cleanrooms in Hyderabad and cleanroom infrastructure in India.
Planning a cleanroom in Telangana or Andhra Pradesh?
Frequently asked questions
- What is an ISO 14644 cleanroom class?
- It is a cleanliness rating from ISO 1 (cleanest) to ISO 9, based on the maximum number of airborne particles of given sizes allowed per cubic metre of air. Each class allows ten times more particles than the one before.
- Is ISO Class 5 the same as Class 100?
- Roughly, yes. “Class 100” comes from the withdrawn US Federal Standard 209E and corresponds to ISO 5. Likewise, Class 10,000 is about ISO 7 and Class 100,000 about ISO 8.
- What is the difference between ISO 7 and ISO 8?
- ISO 7 allows up to 352,000 particles of 0.5 µm or larger per cubic metre; ISO 8 allows ten times as many, 3,520,000. In practice, ISO 7 needs several times more air changes and HEPA coverage.
- How do GMP Grades A, B, C and D relate to ISO classes?
- Grade A is ISO 5 at rest and in operation. Grade B is ISO 5 at rest and ISO 7 in operation. Grade C is ISO 7 at rest and ISO 8 in operation. Grade D is ISO 8 at rest, with in-operation limits set by risk assessment. GMP grades also set microbial limits.
- How often must a cleanroom be reclassified?
- ISO 14644-2 defaults to once a year, with longer intervals allowed if a risk assessment and monitoring justify it. Under EU GMP Annex 1, Grade A and B areas are requalified at most six months apart, and Grade C and D at most 12 months apart.
- ISO 14644-1:2015
- ISO classes of air cleanliness, Table 1 · Cleanroom.net
- Cleanroom classifications: ISO, EU GMP and FDA · Eupry
- Cleanroom classification: ISO 14644 vs EU GMP Grades A–D · IntuitionLabs
- Cleanroom classification explained · Aimil
- Environmental monitoring and GMP · News-Medical / Particle Measuring Systems
- India revises GMP rules (Schedule M) · ECA Academy
- Revised Schedule M timelines · India Briefing
- Proposed Schedule M amendment on Grade A limits · ThePrint
- ISO 14644 in semiconductor cleanrooms · TSI
- OSAT facility case study · IMARC Engineering
- Cleanroom assembly for Class II and III devices · LSO
- Ceiling filter coverage and air changes · Angstrom Technology
- ISO and FS 209E comparison · Terra Universal
- ISO 7 and ISO 8 medical cleanrooms · Xometry